UL’s European Center of Excellence for Fire Resistance

Steelwork protection

Fire protection of structural steelwork: Cellulosic and hydrocarbon testing, evaluation and certification.

UL has been at the forefront of testing and certifying the fire protection of structural steel for ‘standard’ buildings and for petrochemical installations for more than 30 years. 

Testing capabilities

ANSI/UL 263 – the default Standard for North America

For North American building codes, ANSI/UL 263 is the default Standard for evaluating fire protection of structural steelwork. ANSI/UL 263, the Standard for Safety of Fire Tests of Building Construction Materials, and ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials, were developed to simulate a building fire, often referred to as a “cellulosic fire.” The CAN/ULC-S101 Standard, Standard Methods of Fire Endurance Tests of Building Construction and Materials provides equivalent test requirements for the testing of building materials to ensure market access across North America. 

These Standards were developed to simulate the type of fires that occur in commercial buildings, such as offices, hospitals and schools.  These are often referred to as ‘cellulosic fires’ due to the nature of the contents typically found in a commercial office building or multi-dwelling residence.  

At five minutes, the temperature within the furnace reaches 538°C (1,000°F). The temperature gradually increases during the duration of test until at four hours, the temperature within the furnace reaches 1093°C (2000°F). This is considered to be the ‘standard’ time/temperature curve for buildings. Vertical fire resistive assemblies are also subjected to the hose stream test which is specific to these Standards.  

Petrochemical industry – ANSI/UL 1709 Certification

Over the last two decades, the ANSI/UL 1709, the Standard for Rapid Rise Fire Tests of Protection Materials for Structural Steel, for structural steel fire protection has grown in importance across the worldwide petrochemical industry. The Standard is currently considered the default fire resistance test standard in many parts of the world, particularly those that actively use American Petroleum Institute (API) guidance for the petrochemical industry. 

Certification for Hydrocarbon Ratings

We have been certifying products to the ANSI/UL 1709 hydrocarbon Standard for more than 25 years, but legislation and guidance in many parts of the world impose additional requirements on the products that the current test method is unable to fully address.  
To keep our Certification relevant to the needs of the industry, we have developed a wider suite of characteristics for steelwork protection when used in petrochemical-type installations. These characteristics have been collated into our new hydrocarbon certification service. The UL category for this service is BYFH.

The service includes the following mandatory requirements: 

  • ANSI/UL 1709 testing and certification
  • Environmental durability testing to UL 2431, Standard for Durability of Fire-Resistive Coatings and Materials 

The service also includes a number of optional characteristics that can be addressed within the scope of the certification such as:

  • Alternative hydrocarbon fire exposure conditions such as BS 476: Part 20: Annex D
  • Jet fire exposure to ISO 22899-1
  • Norsok M501
  • Multi-Temperature Analysis (MTA)

British Standard 476: Part 21 Testing & Certification

In addition to testing and certification for North American code compliance, we offer testing, assessment and product certification services to BS 476: Part 21. Our team is experienced in certifying to this standard and is well positioned advise how to maximize your testing and certification investment. We have facilities in North America and in Germany, our new, state-of-the-art laboratory in Rosenheim that can be used to test products to BS 476: Part 21.

ANSI/UL 2431 – Environmental Durability  

Facilities are often placed in more challenging natural environments such as extreme heat or cold, or near oceans requiring that the products used in the buildings be stable when exposed to these various environmental factors. This is especially important when the products provide a life safety function such as fire protection. ANSI/UL 2431, the Standard for Durability of Fire-Resistive Coatings and Materials, is used to evaluate the protective coating against the long-term effects of environmental exposure, often a critical factor in the performance of materials as well as vibration and impact. The method is already a mandatory requirement within ANSI/UL 1709. 

Multi-Temperature Analysis

Certification may also include product design tables for alternate critical core design temperatures. This is achieved by conducting an evaluation of the test data called the Multi-Temperature Analysis (MTA). This analysis identifies the thickness of coating material necessary to keep a specific substrate below a specific temperature for a precise duration.  This analysis is in line with the philosophy of ANSI/UL 263 and ANSI/UL 1709 but does not restrict the limiting steel temperatures to 593°C/704°C (1100°F/1300°F) and 538°C/649°C (1000°F /1200°F) for beams and columns respectively.  

The results relating to the Multi-Temperature Analysis are published as supplemental information to the main certification design and are often used in performance-based fire protection applications when a specific fire protection requires a specific level of fire protection due to the different heat exposure generated from the anticipated fuel source.  In order to accommodate this exposure, alternate critical core temperature designs for products have been developed at various temperatures ranging from 371°C-760°C (700°F-1400°F) in increments of 38°C (100°F). 

Cell Beam Evaluation & Certification 

UL is now able to provide evaluation of structural cell beams (beams with cut-outs within the web) to BS and EN Standards and codes. We deliver this evaluation via a bespoke software program developed by structural engineers. This program enables us to evaluate any configuration of web cut-outs to determine the likely failure time. This is possible against any given failure temperature specified by the client.

EN 13381 Testing & Certification

The EN 13381 series of standards make it possible to demonstrate European compliance for the fire protection of structural steelwork. This series covers:

  • Applied passive protection to steel members 
  • Applied protection to concrete-filled hollow steel columns 
  • Applied reactive protection to steel members
  • Applied fire protection systems to steel beams with web openings

We can offer expertise regarding this testing to deliver an optimal test package for subsequent evaluation.

Certification of steelwork fire protection products

UL certifies steelwork fire protection products under the following product categories. Click on the category code links to view UL Guide information for that product category. The guide information also has links to manufacturers whose products are certified under that particular category. To view all UL certifications (e.g. Listings and Classifications) see the UL Online Certifications Directory at www.ul.com/database.

Category Name

Cellulosic Fire Test Standard

Hydrocarbon Fire Test Standard

Environmental Exposure Test Standard

UL Category

Code

Epoxy Mastic and Intumescent Coatings

UL 263

UL1709

UL 2431

Spray-applied Fire-resistive Materials

UL 263

UL1709

UL 2431

Hydrocarbon Fire Protection

 

UL 1709

UL 2431

Topcoats

UL 263

UL1709

UL 2431

Mineral & Fiber Boards

UL 263

UL1709

 

CERZ

Mat Materials

UL 263

UL1709

 

CEAV

Building Units

UL 263

UL1709

 

BZXX

Sprayed Reactive Intumescent Coatings Certified to the ASFP Yellow Book

BS 476: Part 20/21

 

 

EAD 350140-00-1106 - Renderings and rendering kits for fire resisting applications

EN13381-4/8

 

 

EAD 350142-00-1106 - Fire protective board, slab and mat products and kits

EN13381-4/8

 

 

EAD 350402-00-1106 - Reactive coatings for fire protection of steel elements

EN13381-4/8